Instruction Manual for SUPERLINE series battery back-ups
2010/01/13
www.ever.eu
40
TECHNICAL DATA
PARAMETERS \ MODEL
SUPERLINE
model 6k
SUPERLINE
model 8k
SUPERLINE
model 10k
SUPERLINE
model 12k
Output power
1)
6 kVA
4.8 kW
8 kVA
6.4 kW
10 kVA
8 kW
12 kVA
9.6 kW
GENERAL INFORMATION
Topology VFI
Overall efficiency for Pmax (for VFI) > 93 %
Overall efficiency for Pmax (for ECO) > 98 %
Cooling Forced, internal fans
Degree of protection IP20
Working environment Dedicated rooms with low pollution level
Operating temperature
2)
10 ÷ 40 °C
Storage temperature 0 ÷ 40 °C
Relative humidity for operation < 95 %
Relative humidity for storage < 95 %
Altitude (above sea level)
3)
< 1000 m
RECTIFIER
Input voltage ~70 ÷ 280 V ± 2 %
Frequency of input voltage 45 ÷ 55 Hz ± 1 Hz
Power Factor (PF) > 0.99
Total harmonic distortion of input current
(THDi)
< 3%
Safeguards Overcurrent switches for the basic and BYPASS lines 2 x 63 A (ch.B)
INVERTER
Output voltage (effective value) ~230 V ± 2 %
Shape of output voltage Sinus
Frequency of output voltage Synchronous / 50Hz ± 0.2 Hz
Static control of voltage < 1 %
Total harmonic distortion of output voltage
(THDu)
< 1,5 % for Pmax (line)
< 5 % for Pmax; CF = 2.2; PF=0.65)
Peak factor 5:1
Short-circuit current > 5 I
N
Safeguards
Inverter operation – electronic safeguards against shorting and overloads
BYPASS line operation – output overcurrent safeguards
ACCUMULATORS
Battery back-up’s accumulators
1 x 28 x VRLA 12 V / 7 Ah
2 x 28 x VRLA 12 V / 7 Ah (option)
Support time with internal batteries only
(100%/80%/Pmax)*
> 12/21/35 min
> 24/32/54 min
> 9/12/25 min
> 17/22/40 min
> 7/10/15 min
> 13/17/30 min
> 7/10/12 min
> 10/14/25 min
Support time with 1 battery module installed
(100 % / 80%/50% Pmax)
> 72/95/180 min > 50/72/125 min > 40/51/92 min > 30/42/74 min
Maximum charging time of internal batteries
4)
< 2h < 2h < 2h < 2h
Maximum charging time of 1 module
(after discharging with power of 80% Pmax)
4)
< 3h < 3h < 3h < 3h
MECHANICAL PARAMETERS
Dimensions (w x d x h) 340x740x795mm
UPS weight 200 kg
EQUIPMENT
Connectors Screw terminals; max. 16 mm
2
(line)
Signalling Acoustic and visual, LCD display
Communication interface RS232, USB, SNMP/HTTP network control card - optional
EPO Available
Manual BYPASS switch Available
Note: The manufacturer reserves the right to change the abovementioned parameters without notice.
Notes:
1)
For normal operation of the battery back-up the load connected to its output should not exceed 80% of value indicated in the table. Reserve power is essential to
ensure continuous operation of connected devices in case of momentary rushes in load current.
2)
Continued exposure of the battery back-up to the temperature of the surrounding exceeding +25°C will shorten the life of batteries.
3)
If the altitude above sea level increases beyond the provided limit the permitted load power of the batter back-up decreases.
4)
Time to charge the batteries to 90% capacity after discharging them with load of 80% Pmax
5)
Sample battery module in a typical configuration.